What size opening do you need for a ridge vent?

Short answer. The opening has two dimensions: the width of the slot, typically about 1 inch on each side of the peak, and the length, which must be long enough that the vent's rated net free area meets the attic's exhaust requirement. For a balanced system, required exhaust in square inches is roughly the attic floor area times 0.24; divide that by the vent's rating per foot to get the minimum slotted length.

Worked examples

Counting usable length

Only the slotted length counts. Subtract the uncut ends, often about 6 inches at each gable end and about 12 inches at walls and chimneys, plus any ridge over spaces that do not connect to the attic, such as a vaulted porch.

When the ridge is too short

Do not widen the slot to compensate

Cutting wider than the instructions specify does not raise the vent's rated airflow and can let water in. If the math still comes up short, the honest answer may be a different exhaust plan rather than a bigger hole. Read roof ventilation basics and how roofers measure a roof.

In depth

Does a hot Georgia attic shorten the life of your shingles?How hot Georgia attics and shingles get, what research says about ventilation and shingle life, and when radiaHow much attic ventilation does a Georgia roof need?Attic ventilation for Georgia homes: intake and exhaust balance, the IRC R806 1/150 and 1/300 rules with workeRidge vent or box vents: which is better, and can you use both?Ridge vents vs box vents, turbines and power fans for Georgia attics: how each works, why mixing exhaust types