What do building regs say about roof ventilation?

Short answer. Under the International Residential Code, which Georgia uses with state amendments, a vented attic needs net free vent area of at least 1/150 of the attic floor area, or 1/300 when 40 to 50 percent of it is in upper vents near the ridge and the rest is low at the eaves. The code also sets screen opening sizes and requires an air space above the insulation at the vents.

The numbers in plain terms

A worked example

A 1,800 square foot attic at 1/300 needs 6 square feet, or 864 square inches, of net free area: roughly 432 square inches of exhaust up high and 432 of intake down low. Net free area is the open area rated by the vent maker and printed on the product, not the vent's outside size, so a vent that looks big may count for much less.

The other option

The code also allows unvented attics (R806.5), where insulation such as spray foam goes against the underside of the roof deck and the attic becomes part of the conditioned space. That is a whole assembly with its own requirements, not a fix for a poorly vented attic.

How the pieces fit together is in roof ventilation basics, and why it matters for shingle life is in attic heat and shingles.

In depth

How much attic ventilation does a Georgia roof need?Attic ventilation for Georgia homes: intake and exhaust balance, the IRC R806 1/150 and 1/300 rules with workeRidge vent or box vents: which is better, and can you use both?Ridge vents vs box vents, turbines and power fans for Georgia attics: how each works, why mixing exhaust typesDoes a hot Georgia attic shorten the life of your shingles?How hot Georgia attics and shingles get, what research says about ventilation and shingle life, and when radia

People also ask