How do you measure whether your attic has enough ventilation?

Short answer. Measure the attic floor area, add up the net free area of every intake vent and every exhaust vent, and compare the totals to what the code calls for: 1/300 of the floor area when intake and exhaust are balanced, or 1/150 when they are not. If either side falls short, or exhaust is larger than intake, the attic does not have enough working ventilation.

Step 1: the attic floor area

Use the footprint of the attic, which is usually the footprint of the house under that roof, not the roof area. A 40 by 50 foot ranch has about 2,000 square feet. Treat separate attic spaces, such as one over a garage behind a fire wall, separately.

Step 2: inventory the vents

Ratings are on the vent or its packaging. If they are not visible, a roofer can identify the product or estimate conservatively.

Step 3: compare

For 2,000 square feet on the balanced path, you need about 960 square inches total, at least 480 of it intake and about 480 of exhaust within 3 feet of the ridge. If all vents are high or all are low, the requirement doubles.

Step 4: subtract what is blocked

A vented soffit panel over solid plywood counts as zero. So does a soffit bay packed with insulation. Ventilation on paper means nothing if the path is closed.

The ratios are explained in roof ventilation basics; exhaust choices in ridge vent vs box vents.

In depth

Does a hot Georgia attic shorten the life of your shingles?How hot Georgia attics and shingles get, what research says about ventilation and shingle life, and when radiaHow much attic ventilation does a Georgia roof need?Attic ventilation for Georgia homes: intake and exhaust balance, the IRC R806 1/150 and 1/300 rules with workeRidge vent or box vents: which is better, and can you use both?Ridge vents vs box vents, turbines and power fans for Georgia attics: how each works, why mixing exhaust types