How do you measure whether your attic has enough ventilation?
Step 1: the attic floor area
Use the footprint of the attic, which is usually the footprint of the house under that roof, not the roof area. A 40 by 50 foot ranch has about 2,000 square feet. Treat separate attic spaces, such as one over a garage behind a fire wall, separately.
Step 2: inventory the vents
- Ridge vent: open slot length times the vent's rating per foot.
- Box vents: count times each vent's rating, often around 50 square inches.
- Soffit: the panel's or vent's rating times its length or count.
- Gable louvers: rated area, often smaller than the louver looks because of slats and screen.
Ratings are on the vent or its packaging. If they are not visible, a roofer can identify the product or estimate conservatively.
Step 3: compare
For 2,000 square feet on the balanced path, you need about 960 square inches total, at least 480 of it intake and about 480 of exhaust within 3 feet of the ridge. If all vents are high or all are low, the requirement doubles.
Step 4: subtract what is blocked
A vented soffit panel over solid plywood counts as zero. So does a soffit bay packed with insulation. Ventilation on paper means nothing if the path is closed.
The ratios are explained in roof ventilation basics; exhaust choices in ridge vent vs box vents.